H03VV-F (OMY) / H03VVH2-F 300/300V
Specification
Low voltage multi-core power cables with a rated voltage not exceeding 300/300V. General-purpose cables with thermoplastic polyvinyl chloride (PVC) insulation.
H03VV-F: A flexible cord made according to a harmonized standard (H), rated for 300/300V (03), with PVC insulation (V), PVC sheath (V), and stranded flexible conductors (-F).
H03VVH2-F: A flexible cord made according to a harmonized standard (H), rated for 300/300V (03), with PVC insulation (V), PVC sheath (V), flat (H2), and stranded flexible conductors (-F).
Technical Data
- Conductor: Copper, stranded, flexible class 5 (according to EN 60228)
- Insulation: PVC, type TI1 (according to EN 50363-3)
- Sheath: PVC, type TM2 (according to EN 50363-4-1)
- Operating temperature: Up to +70°C
Standards / Specifications
- Standard: PN-EN 50525-2-11
- The cables meet the requirements of the REACH Regulation and RoHS Directive.
Technical Characteristics
| No. of Conductors x Nominal Cross-section | Single Wire Diameter | Resistance at 20°C | Insulation Wall Thickness | Sheath Wall Thickness | Outer Cable Diameter (max.) |
|---|---|---|---|---|---|
| mm | mΩ/m | mm | mm | mm | |
| H03VV-F | |||||
| 2 x 0.5 | 0.21 | 39.0 | 0.5 | 0.6 | 4.6 – 5.9 |
| 2 x 0.75 | 0.21 | 26.0 | 0.5 | 0.6 | 4.9 – 6.3 |
| 3 x 0.5 | 0.21 | 39.0 | 0.5 | 0.6 | 4.9 – 6.3 |
| 3 x 0.75 | 0.21 | 26.0 | 0.5 | 0.6 | 5.2 – 6.7 |
| 4 x 0.5 | 0.21 | 39.0 | 0.5 | 0.6 | 5.4 – 6.9 |
| 4 x 0.75 | 0.21 | 26.0 | 0.5 | 0.6 | 5.7 – 7.3 |
| H03VVH2-F | |||||
| 2 x 0.5 | 0.21 | 39.0 | 0.5 | 0.6 | 3.0 x 4.9 – 3.7 x 5.9 |
| 2 x 0.75 | 0.21 | 26.0 | 0.5 | 0.6 | 3.2 x 5.2 – 3.8 x 6.3 |
Other Products: